Plan submitted for a new 80 device monitored fire alarm system going in a new 3 story medical office building. Reviewed using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

2/24/2022 VVitori

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications must be submitted to the Permit Center as a resubmission for the original project.

Effective 1/01/2022 you must include a written response to comments summary to clarify and illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

Resubmittals will not be approved without a response to comments. 

2/24/2022 VVitori

1) Pull station at front door is approximately 8' from main entrance/exit. Provide pull station within 60". 101:9.6.2.3

Thursday, February 24, 2022  Hand written response to comments indicate "Relocated pull station to be in door/window frame".

Shown on FA.03.

2/24/2022 VVitori

2) Do not see where sprinkler backflow will be electronically supervised. Show/indicate backflow will be electronically supervised. 101:8.6.7(4), 101:38.3.6.1, 101:38.2.5.2.1 and sprinkler design criteria page FP0.1.

Thursday, February 24, 2022  Hand written response to comments indicate "Page FA.03 shows backflow field verify location".

2/24/2022 VVitori