| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for new 760 head wet (light and OH1) sprinkler system. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
NOTE: all canopies non combustible A-3.2 and A3.4.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
|
1) Design criteria calls for an electric 480v 3 phase 10hp fire pump to provide 300gpm at 15ft of head. Page FP-01 Item 2k. Either: a) show fire pump required by the EOR OR b) provide signed and sealed documentation from the EOR indicating that a fire pump is not needed.
|
| |