Clearance Sheet C2021-005643

 Department IssuesSigned OffIntl

Plan reviewed for new building 8,450 SF Type IIB Construction, Non-Sprinkled, Storage Shell Building. Units 1, 2, 3 will be vanilla box with out demising walls and no bathroom. Unit 4 will have a 1 hour demising wall between unit 3 and 4 with power and bathroom.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC. Reviewed using chapter 42 (storage) of NFPA 101.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

Wednesday, January 26, 2022 DF: Review of 1st resubmittal.

1/26/2022 dfeagle

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

1/26/2022 dfeagle

1) No clearance sheet provided with submittal.

Provide Clearance Sheet.

1/26/2022 dfeagle

2) Sheet A1 shows the building as having two addresses: 5870 & 5880.

a) What is the correct address for this building?

b) Correct plans to reflect correct address.

Wednesday, January 26, 2022 DF: 911 address is 5880 US 1 N.

1/26/2022 dfeagle

3)What is the classification of hazards for this building / units according to Section 6.2 of NFPA 101? 101:42.1.5

Wednesday, January 26, 2022 DF: Response: No tenant at this time.

1/26/2022 dfeagle

4) Sheet A2 provides a door and hardware schedule. The hardware schedule does not provide enough information to determine if the locking arrangement will comply with NFPA 101:7.2.1.

Provide the make and model of the latch and locking arrangement.

The door’s latching/locking arrangement is required to be of a One Releasing Mechanism (integrated lock and latch) and shall open the door leaf with no more than one (1) releasing operation.
Example: You should be able to open a “locked” door by turning the door handle and push/pull open the door leaf “without” unlocking the door first. 101:7.2.1.5.10.2

Wednesday, January 26, 2022 DF: Response: Panic bar on rear, deadbolt & knob on front.

1/26/2022 dfeagle

**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Each new Fire Wall, Fire Barrier, Fire Partition, Smoke Barrier, Smoke Partition, or any other new wall required to have protected openings shall be permanently identified with signs or stenciling above any decorative ceiling and in concealed spaces with the wording, "FIRE AND SMOKE BARRIER - PROTECT ALL OPENINGS", or similar language. Such signs or stenciling shall be 4 inch high letters, 1/2 inch stroke, and not more than 15 feet on center. NFPA 101 8.3.2.4

If wall is fire rated, also add sign that indicates rating in hours.

1/26/2022 dfeagle

**INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- Wall and ceiling finish will meet Class A, B or C. 101:42.3.3.2

- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:42.3.3.3.1

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

1/26/2022 dfeagle

5) Emergency light needed in unit 4's Bathroom. 101:42.2.9

Wednesday, January 26, 2022 DF: NO RESPONSE. NOTE: an emergency light is required in the bathroom. The Fire Inspector will verify compliance at time of the Fire Final.

1/26/2022 dfeagle