SJC Home
Clearance Sheet C2021-004155

 Department IssuesSigned OffIntl

Plan submitted for 79 head wet nfpa 13 sprinkler . Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) Floor plan shown on this sprinkler submittal does not match approved building plans. Provide plans that match previously approved layout. Ex - Right tenant space of sprinkler plans show rest room on left while approved building plans show no restroom in this unit.  This submittal also shows suite B2/B3 as open and vacant yet the approved building plans show B2 and B3 subdivided with restrooms.