Clearance Sheet C2021-003540*004

 Department IssuesSigned OffIntl

Plan reviewed for new fire alarm system: FACP - Notifier NFW-50X w/communicator, SAFE PATH 4 Facility Communications SP40S, SAFEPATH 4 Addressable Paging, Speaker & Telephone Splitter.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

4/14/2022, Resubmission Reviewer: Aaron Connell 904-599-8253, aconnell@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

4/14/2022 aConnell

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

4/14/2022, A Connell: Responses to all comments have been submitted with the resubmittal as well as new plans page with the old plan marked "OLD".

4/14/2022 aConnell

1) Occupant Load shown on sheet FA1.1 is 130 occupants. Construction documents sheet A0.3 shows the occupant load at 404 occupants (NFPA 101).

Update sheet FA1.1 to reflect correct occupant load.

4/14/2022' A Connell: Noted that the re-submitted plans have been adjusted to note the 404 occupancy load.

4/14/2022 aConnell

2) Construction document sheet E0.4 in the Fire Alarm Notes states the CO detectors will have a different sound than that of the Fire Alarm System.

Be prepared to demonstrate the different sound that will not be comparable / mistaken for the fire alarm system.

4/14/2022, A Connell: Noted that the resubmitted plans notes have been adjusted to reflect "Rev-1" CO Detector: "*LOCAL AUDIBLE ALARM WITH TEMPORAL 4 CODE"

4/14/2022 aConnell

3) The Fire Line Backflow Preventer's control vales are to be supervised. The plans and the fire alarm riser do not show the BFP's Valves are being supervised. 101:9.77.2

Demonstrate on the plans the BFP's control valves are supervised.

4/14/2022, A Connell: Noted that the re-submitted plans now show the back-flow preventer control valves being monitored/supervised.

4/14/2022 aConnell

4) No manual pull station show at the left rear exit door by the restrooms.

4/14/2022' A Connell: Noted resubmitted plans Sheet FA1.1 now reflects a Fire Alarm Pull Station at the left rear exit door.

4/14/2022 aConnell