SJC Home
Clearance Sheet C2021-003540*003

 Department IssuesSigned OffIntl

Plan reviewed for Revision to approved plans to remove lightning protection system.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

 

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) Received sheet E4.1 for Permit #12114021 (Daycare and Salon Building) and Sheet E4.1 for permit 12113114 (Private Garage Building). I do not see the second (2nd) sheet (Job Copy) for the Daycare and Salon. The building department has stamped Sheet E4.1 (Private Garage) as the Job Copy for this revision (this sheet does not belong with this revision plan set).

a) Remove Sheet E4.1 for the Private Garage from the Daycare and Salon Revision set and replace it with the correct Sheet A4.1 for the Daycare and Salon.

b Provide the "OLD" Sheet for the Private Garage with the resubmittal.