SJC Home
Clearance Sheet C2021-003540*003

 Department IssuesSigned OffIntl

Plan reviewed for new fire alarm system for a daycare. FACP - Notifier NFW-50X Addressable, Remote annunciator - Notifier N-AAN-80.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

4/14/2022, Resubmission Reviewer: Aaron Connell 904-599-8253, aconnell@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

4/14/2022 aConnell

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

4/14/2022, A Connell: Responses to all comments have been submitted with the resubmittal.

4/14/2022 aConnell

1) Plans do not indicate the Back Flow Preventer's control valves are being monitored for tamper. 101:16.3.6(2) & (5)(a)

Adjust the plans to show the BFP's control valves are being monitored for tamper.

4/14/2022, A Connell: Noted that the re-submitted plans now show the back-flow preventer control valves being monitored for tamper.

4/14/2022 aConnell