 Joe Maguire 373-9257 Coastal Utilities

Plan APPROVED for private underground fire main (2575' 10" DR-18, 265' 6" DR-18, 130' 4" DR-18)  in complex starting with 10" DCDA BFP (to be electronically monitored by others) and supplying 4 private fire hydrants, and to 6" PIVs and fire sprinkler in-building risers to 8030 sqft storage bldg. and 5812 sqft daycare/salon. These two buildings each have freestanding FDCs with check valves connected by 4" from the risers.

Once building plans have been submitted for the Collision Center and Sales/Detail Center, a revision can be submitted to cover the two fire sprinkler lines to these buildings. (Both of these buildings have their FDCs on the buildings)

ATTENTION FIRE PLAN REVIEWER: SPRINKLER RISERS REQUIRED TO HAVE CHECK VALVE

1/4/2022 SMurray