Clearance Sheet C2021-002491*001

 Department IssuesSigned OffIntl

Plan submitted to add 1 head for build out of a storage space. Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Reviewer: V.Vitori   
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.

NOTE: SPrinkler review of the 1 head was not conducted.

10/27/2022 VVitori

1) Due to the change of occupancy (shell designed for mercantile to storage), method, arrangement, height of commodities being stored this requires an engineering evaluation. While an owners certificate was provided signed by the owner only, you will need to first submit both of the following before a sprinkler review can begin:

a) a copy of the owners certificate completed by the owner and architect. Also it will need to be sign/sealed by the sprinkler engineer. (We do not accept electronic signatures at this time.)

b) a signed and sealed letter from the sprinkler engineer addressing if changes are needed to the existing sprinkler system. If changes are required he will need to articulate those changes.25:4.1.6

NOTE: This message was conveyed in a meeting on 9 15 22 at 2p (same day these sprinkler plans were turned in) with architect, Jason Canning and fire protection engineer, Mr. Alan Watts.

Thursday, October 27, 2022 Letter received dated Oct 10 20222 by Mr Alan Watt indicates "The existing system will work if storage height is limited to 12 feet above the floor, 5 feet for mattresses. An increase above 12 feet of storage will require a hydraulic redesign to see if the existing piping is adequate for the amount of water required, all sprinkler heads will have to be replaced and a row of in-rack sprinklers may be required."

10/27/2022 VVitori

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

10/27/2022 VVitori