 Department IssuesSigned OffIntl

Plans for a 6 device fire alarm system intended only to monitor the fire sprinkler system utilizing a Potter PFC 6006 conventional panel.  The backflow preventer is also being monitored. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

1/10/2022 PWebb

The plans indicate the fire alarm panel and riser in a location that does not exist in the previously approved building plans.  Unable to approve the fire alarm plan until the original building plans are revised to add the new riser and panel room.  

--------------

Building plan revision has been submitted to add a small riser room in the corner of the exercise studio, indicated by highlighter.  Per the contractor that location does not change the room layout indicated on the plans.  PJW Monday, January 10, 2022

1/10/2022 PWebb