SJC Home
Clearance Sheet C2021-000976

 Department IssuesSigned OffIntl

Plans for a 155 head NFPA 13 fire sprinkle system for a clubhouse building.  The system will have a 4 inch riser with the FDC being mounted remotely,  tied into the underground. The system is designed as all wet, at .10 density for the building and the attic with 3 remote areas.   


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

11/30/2021 PWebb

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

11/30/2021 PWebb

1) The sprinkler criteria sealed by James M. Curtis PE, specifies .15 gpm over remote 1500sf.  The plans indicate .10 at around 1000sf.   

 

Florida Administrative Code (FAC) 61G15-32.002 defines a material deviation as "Any deviation from the design parameters established and documented by the Engineer of Record." Furthermore FAC 61G15-32.003(6) states "When layout documents contain material deviation from the Engineer of Record's Fire Protection System Engineering Document, such layout documents are not compliant unless they are accompanied by revised Engineering Documents made and sealed by the Engineer of record for the Fire Protection System."

----------------

The criteria was revised to the .10 density.  PJW Tuesday, November 23, 2021

11/23/2021 PWebb

2) Plans do not indicate relieve valve or auxiliary air reservoirs per NFPA 13:7.1.2.  Provide specifications. 

----------------------

Specifications submitted for a relief valve integrated into the main drain/test valve.  PJW Tuesday, November 23, 2021

11/23/2021 PWebb

3) How will the attic be maintained above 40 degrees?  NFPA 13 8.16.14

Provide documentation from the EOR supporting the method chosen. 

----------------------------

Plans indicate that the attic will be insulated with icynene insulation.  Reached out to the EOR and left message to get documentation from him verifying that this method will maintain the system above freezing.  PJW Tuesday, November 23, 2021

--------------------------

Also sent email to contractor attempting to get this information.  PJW Wednesday, November 24, 2021

11/30/2021 PWebb

4) NFPA 13 9.2.1.3.3.2  Provide spec sheet for suspended ceiling tile grid showing it meets ASTM C 635.

NFPA 13 9.2.1.3.3.4 *   Where flexible sprinkler hose fittings are used to connect sprinklers to branch lines in suspended ceilings, a label limiting relocation of the sprinkler shall be provided on the anchoring component.
An example of language for the label is as follows: CAUTION: DO NOT REMOVE THIS LABEL.Relocation of this device should only be performed by qualified and/or licensed individuals that are aware of the original system design criteria, hydraulic criteria, sprinkler head listing parameters, and knowledge of the state and local codes including NFPA 13 installation standards. Relocation of the device without this knowledge could adversely affect the performance of this fire protection and life safety system.

-------------------

Armstrong spec sheets provided meeting the above.  PJW Tuesday, November 23, 2021

 

11/23/2021 PWebb

5) Informational no response necessary. 

The FDC is approved as a yard FDC.  Specs have been provided with a Wall mount FDC starred. 

11/23/2021 PWebb

6) Identify rood pitches on the plans, as well as the roof spans that the heads are covering in accordance with the attic head specs.

----------------

The roof spans were indicated but the roof pitches did not appear to be.  I verified the roof pitches form the original construction plans.  The pitch does fall into the allowable range of the heads.  PJW Tuesday, November 23, 2021 

11/23/2021 PWebb

7) The sectional view provided does not show the sprinkler layout.  NFPA 13:23.1.3(4).

-------------

Sprinkler layout added to the sectional view.  PJW Tuesday, November 23, 2021

11/23/2021 PWebb

8) Provide specs for the test/drain assembly. 

-------------------

Provided.  PJW Tuesday, November 23, 2021

11/23/2021 PWebb