Plan reviewed for New wet sprinkler system. 4 inch shotgun riser with attic protection, dry pendants over the porch and awning.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

10/14/2021 dfeagle

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

10/14/2021 dfeagle

1) How will the sprinkler in the attic including the upper attic space be maintained above 40 degrees F.? 13:8.16.4.1

Thursday, October 14, 2021 DF: Received an letter from David Blake, CET NICET Cert#103056 clarifying the attic will remain above 40 degrees F as the attic roof deck is insulated with Icynene.

10/14/2021 dfeagle

2) How will you protect the sprinkler riser room maintained above 40 degrees F? 13:8.16.4.1

Thursday, October 14, 2021 DF: Per contractor the buildings mechanical equipment is in this room and the room is conditioned.

10/14/2021 dfeagle

3) Plans do not call out the relief valve. 13:7.1.2.1

Provide the cut sheet(s) for the Inspector's Test & Drain and the relief valve.

10/14/2021 dfeagle