SJC Home
Clearance Sheet C2021-000976*002

 Department IssuesSigned OffIntl

Plan reviewed for Installation of 6 inch fire main with DCDA BFP, one fire hydrant, one FDC to 1 foot AFF at Clubhouse and, 6 inch reduced to 4 inch at FDC for pool house to 1 foot AFF at pool house.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

Tuesday, August 10, 2021 DF: Review of 1st resubmittal. NOTE: All new plan sheets provided. One old set of plans provided.

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) Plans submitted with a Fire Marshals Miscellaneous Review Permit Application. Fire service mains are to be applied for with the Fire Marshals Private Fire Service Systems and/or Water Main…

Provide the appropriate FM permit application(s).

Tuesday, August 10, 2021 DF: Clubhouse underground permit application provided. No application for the pool pavilion.

Tuesday, August 10, 2021 1120 Hrs. DF: Spoke with Elliot Jones via phone regarding this comment. I agreed to hold the plans until Thursday noon before rejecting to provide time to provide an additional permit application for the Pool House.

 

2) The fire mains for each building will need to be permitted separately as each underground is tied to their respective building. The way the BFP, fire mains, FDC’s and hydrant is laid-out in this plan set, two permits would be needed.

For example: The clubhouse could have the fire main and its underground including the hydrant and its FDC on one permit. The pool house could have its underground main and it’s FDC on the pool house’s FM permit.

Indicate on the plan set which section / portion of the fire main, FDC, Hydrant, etc. is for which permit.

8/10/2021 dfeagle

3) Missing 2nd set of manufacturer’s specification’s sheets.

8/10/2021 dfeagle

4) Sheet C6 has Special Notes: 2. “Approval of these plans do not include approval for private underground water mains, fire hydrants and fire sprinkler mains.

This note needs to be removed from this set of construction plans before I can approve this set of plans.

8/10/2021 dfeagle

5) Enlarged Plan on sheet C6: Once the fire main reduces from 6” to 4” I am not able to see / follow the fire main connections to the clubhouse. Plans indicate the Pool house fire protection line over 4” Clubhouse FDC Supply Line.

a) Provide an enlarged plan showing the fire main and pool house fire mains their connections and how the FDC’s for each building are connected to those fire mains.

b) If the FDC will have separate lines to the building, show those lines on the plans.

c) Show control (isolation) valves for the clubhouse and for the pool house. NOTE: If the FDC is connected to the clubhouse and/or pool house mains, show the isolation valves BEFORE (fire main side) the FDC’s. 24:5.9.3.2

d) Show check valves on the FDC lines on the main/supply side of the FDC. 24:5.9.3.1

Tuesday, August 10, 2021 DF: Item c) A control valve (gate valve) has been added to the 6" Fire Service line after the fire hydrant line and before the 6"x4" tee to the Clubhouse fire line. This valve will shut down fire service line to both the Clubhouse and Pool pavilion. A control valve needs to be provided for each buildings fire service line.

The control (gate) valve(s) should be on the individual buildings fire service lines. Fore example, the Clubhouse should have the isolation valve on the clubhouses 4" line and the Pool House should have its isolation valve on the Pool House 4" fire service line after 6" to 4" reducer.

Tuesday, August 10, 2021 1120 Hrs. DF: Spoke with Elliot Jones via phone regarding this comment. I agreed to hold the plans until Thursday noon before rejecting to provide time to provide an updated sheet identifying isolation valves for each buildings fire service line.

 

6) Special Notes #1 on sheet C6 refers to boiler plate general notes C9.

Provide sheet C9.

8/10/2021 dfeagle

7) There are three (3) models of the DCDA BFR assemblies shown in the manufacture’s spec sheets provided.

Identify which model BFP assembly is being installed.

Tuesday, August 10, 2021 1120 Hrs. DF: Spoke with Elliot Jones via phone regarding this comment. I agreed to hold the plans until Thursday noon before rejecting to provide time to provide an updated spec sheet identifying which model of DCDA is being used.

 

8) The BFP exhibits on sheet GW-1 do not match the type of BFP assembly specification sheets provided.

Provide BFP assembly exhibit representing the type and model of back flow being installed.

Tuesday, August 10, 2021 DF: No specific BFP identified.

 

9) How will you protect the BFP assembly from freezing? 24:6.5.2

a) Provide manufactures spec sheets.

Tuesday, August 10, 2021 DF: Specification sheets for Armacell Armaflex insulation.

8/10/2021 dfeagle

10) Show on the plans the depth the pipe will be buried, measured from the top of the pipe complying with. 24:10.4.2.2

Tuesday, August 10, 2021 DF: See sheet C9: Utility Notes #12.

8/10/2021 dfeagle

11) The hydrant appears to be close to the drive. Provide enlarged exhibit showing the hydrant, drive edge and protective bollards. 24:7.3.5, 24:10.4.2.2.6

Show an exhibit of the bollard placement. Bollards shall be:

a) Constructed of steel not less than 4 inches (102 mm) in diameter and filled with concrete.

b) Not less than 3 ft. (0.9 m) deep in a concrete footing of not less than 15 in. (380 mm) diameter.

c) With the top of the posts not less than 3 ft. (0.9 m) above the ground.

d) The bollards shall be placed in such positions to protect the hydrant from impact from the front and both sides facing / near the drive BUT shall not interfere with the operation of the hydrant and placement of the fire hose.

Tuesday, August 10, 2021 DF: Sheet C6 identifies the hydrant to be minimum 3 feet from the curb.

8/10/2021 dfeagle

12) Missing note identifying the Clubhouse termination 1 foot AFF.

8/10/2021 dfeagle

13) The hydrant exhibits show loose gravel at the bottom of the hydrants where the flat stone or concrete is to be placed. 24:7.3.1, Annex A7.3.1 (Figure A7.3.1)

Provide exhibit(s) showing the flat stone or concrete slab in place.

Gravel is permitted around the sides of the flat stone/concrete slab for drainage.

Tuesday, August 10, 2021 DF: A note has been added to hydrant typical elevation on sheet GW-1.

8/10/2021 dfeagle

14) FDC Note in the Enlarged Plan: “See detail on sheet CW-4. Provide sheet DW 4.

8/10/2021 dfeagle

15) A check valve before or after the 6” to 4” reducer but after the hydrant and before the FDC’s is needed.

8/10/2021 dfeagle

16) Plans indicate a 4” line to the Clubhouse. Applications Description of work states 6” fire riser for Clubhouse? Adjust plans or scope of work for correct size of line to Clubhouse.

8/10/2021 dfeagle