Plan submitted for new Tank overlapping high proximity suppression system protecting a 14' hood with equipment in a 126"x30" zone (unknown equipment arrangement). Reviewed as using FFPC 8th edition effective January 1, 2024. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Reviewer: V.Vitori
For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us.
To schedule fire inspections call 827 6842 (automated system).
Questions about inspections or resubmitting your plans call 209 1740x1.
INSPECTOR: Make sure there is no large/industrial fryers over 14" wide, woks larger than 24", appliances with shelves or solid fuel appliance. If there are the plans will need to be resubmitted for review showing how these devices were covered in accord with the manual. (based on page 22 of tank manual).