Plan reviewed for a New BDA System. ADR (PSR-78-9533-X) Digital Repeater, ADRF-BBL--X Battery Back-up Unit, PSR-ANN-X Annunciator, ClearLink 600-4000 MHz Omni Antenna, Westell 698-640 MHz Antenna

Per approved building plans, Governing Codes Section on the Cover Sheet; Construction Type is VA(V(III)) 1HR. The building's survivability rating is 1 hr. 1225:18.12.3.4

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the permit center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (Job and Office). One copy of the removed/old pages from the JOB Copy will need to be submitted and marked "OLD". Do not forget to remove pages for work not associated to this permit. All plan papers must be the same size.
C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comments was addressed. EX - "Top Left of Page E1-1" or "Page E1 Note 8".
- Code responses shall reference Florida Fire Prevention Code, 7th Ed.

 

1) St Johns County Fire Marshals Office (SJCFMO) uses the 2022 Edition of NFPA 1225 Standard  for Emergency Services Communications instead of NFPA 1221 2016 Edition.

Update the code Compliance section and verify the plans comply with NFPA 1225, 2022 Edition.

 

2) The heat maps provided on Sheets ER5 and ER6 are in greyscale. SJCFMO requires the Heat Maps to be in color.

Provide Heat Maps in color.

 

3) I do not see Manufacturer Spec Sheets for the NEMA Enclosures. Also, I do not see the type of NEMA enclosure called out for each of the NEMA Enclosures shown on Sheet ER1. 1225:18.3.1

a) Call out the NEMA enclosure types on Sheet ER1, AND

b) Provide the manufacturers specification sheets for the enclosures.

 

4) The Surge Protector shown on Sheet ER20 has a UL Listing of UL497E (per spec sheet on PolyPhaser Web Site). NFPA 1225:18.4.2 requires a UL Listing of UL-497C.

a) Provide the manufacturers Spec Sheet demonstrating this unit does meet UL-497C, OR

b) Provide a Lighting Arrestor complying with 1225:18.4.2