Clearance Sheet C2020-007043

 Department IssuesSigned OffIntl

Plan reviewed for 5200sf construction type IIB mercantile class c. Reviewed as new class c mercantile using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

1/11/2021 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until a permit has been pulled :

- fire alarm system (page E0.0 top right)
- fire sprinkler system (Page A1.4 top right indicates fire riser location)

1/11/2021 VVitori