Plans for a 10' CaptiveAire Type 1 Kitchen Hood Model 5424-ND-2-PSP-F. It will utilize listed CaptiveAire duct.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
|
1. Provide a floor plan of the space indicating the location of the hood.
|
| |
|
|
2) The plans indicate to use CaptiveAire model DW listed duct, unless the 18" clearance to combustibles is not met then the DW-2R double wall is required. Which one are you using?
|
| |
|
|
3) What is the wall behind the hood and the cooking equipment constructed of? Demonstrate compliance with NFPA 96:4.2 or 4.2.3 all the way from the top of the hood to the floor.
|
| |
|
|
4) What gauge metal is the hood. NFPA 96:5.1. 18ga steel or 20ga stainless required.
|
| |
|
|
5) Provide a roof plan view indicating the clearances to the items indicated in NFPA 96:7.8.2.1.
|
| |
|
|
6) The exhaust fan does not indicate that it is provided with a hinge, hold open retainer and flexible conduit. NFPA 96:7.8.2.1, 8.1.2.1.
|
| |
|
|
7) How will you ensure that the cooking equipment will be returned to its original location? Demonstrate compliance with NFPA 96:12.1.2.3.1.
|
| |
|
|
8) Provide an elevation view from the hood all the way to the exhaust fan. Indicate any changes of direction, location of cleanouts, and clearance to combustibles. Include a listed duct isometric.
|
| |
|
|
9) NFPA 96:7.8.2.2 requires access on all sides by a flat surface. Unsure what the roof pitch is until the roof plan is provided.
|
| |
|
|
10) Identify the means in which the fan will be activated when any appliance is turned on in accordance with NFPA 96:8.2.3.3
|
| |
|
|
11) Vertical Duct: Identify the height of any required duct openings (cleanouts). If not easily accessible from the ground or a 10’ step ladder, safe access and a work platform will be required per NFPA 96:7.4.2.3.
|
| |