| | Department Issues | Signed Off | Intl |
|
|
Plans for a 450 head NFPA 13 wet aboveground fire sprinkler system for a large ALF. The underground is previously approved. The system is designed with LH and OH remote areas.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
1) The Sprinkler EOR plans submitted with the shop drawings sealed by Ryan L. Chewning PE. show the FDC mounted on the building and show the use of sidewall heads in the units. The shop drawings show a yard FDC and pendent heads in the units. The two must match or the procedures in FAC must be followed. Note: The approved underground plan shows the FDC off the building.
Florida Administrative Code (FAC) 61G15-32.002 defines a material deviation as "Any deviation from the design parameters established and documented by the Engineer of Record." Furthermore FAC 61G15-32.003(6) states "When layout documents contain material deviation from the Engineer of Record's Fire Protection System Engineering Document, such layout documents are not compliant unless they are accompanied by revised Engineering Documents made and sealed by the Engineer of record for the Fire Protection System."
|
| |
|
|
2) The plans indicate no sprinklers under several exterior projections citing 8.15.7.3 of NFPA 13. Provide specifications for the exposed finish material and indicate whether it is non combustible, limited combustible, or fire retardant treated wood.
|
| |
|
|
3) How will the attic and exterior projections be maintained above 40 degrees? NFPA 13:8.16.4.
|
| |
|
|
4) Provide plan cross section/ elevation views for the upper level in accordance with NFPA 13:23.1.3(4). The lower level has been provided.
|
| |
|
|
5) TY3235 spec sheet has been provided (dry pendant) but I do not see that head indicated on the plan head legends.
|
| |
|
|
6) The attic head symbols used on the plan are a circle with a single line through it, and 2 circles with an "x" through them one of which protrudes past the circle. The legend does not show the circle with a dash. Ensure that the symbols match and ensure that all heads are represented on the legend.
|
| |
|
|
7) Verify all attic head coverage and demand in accordance with the specs. I am unable to verify this until the symbols are cleared up. Ensure that all specs are included.
|
| |
|
|
8) Storage 1010 (riser location) is not climate controlled. How will the riser be maintained above freezing?
|
| |