SJC Home
Clearance Sheet C2020-006908

 Department IssuesSigned OffIntl

Plans for a 130 device, addressable fire alarm system for an assisted living memory care facility utilizing a Kidde panel. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

9/8/2021 PWebb

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

9/8/2021 PWebb

1) Audible devices are required in all residential units. NFPA 101:9.6.3.5, 32.2.3.4.3.   Ensure that they meet the 15db above ambient or minimum of 75db as required by NFPA 72.   Will the smoke detectors with low frequency sounder bases sound upon building alarm?

-----------------

Low frequency Horn strobes added, separate smoke detectors added.  PJW Wednesday, September 8, 2021

9/8/2021 PWebb

2) Visible notification is required in the following locations.  NFPA 101:9.6.3.5, 32.2.3.4.3. 

- All residential units
- Office 1007B, 1007, and 1121
- Storage 1010
- Office/Storage 1225
- Laundry 1110

-------------------

Low frequency H/S added to the above.  PJW Wednesday, September 8, 2021

9/8/2021 PWebb

3) I do not see a tie in to the kitchen suppression.  Add to the plans and matrix. 

--------------

Kitchen suppression added to the plans/matrix.  PJW Wednesday, September 8, 2021

9/8/2021 PWebb

4) The following door were indicated on the original building plan review that they were going to be locked down, which is permitted.  But in turn it required that the door locks be released upon alarm.  It appears that some of the doors have magnetic hold opens which is fine, but the doors below must unlock upon alarm.  Demonstrate on the plans. 

Doors
1000A
1015
1100
1101
1113
1130
1138
1200
1201
1211
1230
E1002 (Rear gate at memory garden)

------------------

Note added to the plans indicating that all doors will be released upon alarm.  This will be verified at the time of final for each of the above doors including the exterior gate.  PJW Wednesday, September 8, 2021

9/8/2021 PWebb