INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. 101:7.9.2
***With my experience, a typical wall pack emergency light usually mounted 8' above the floor covers approx. 8' either direction with a 3' wide path.***
INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- wall and ceiling finish will meet Class A, B or C. 101:12.3.3.3.
- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:12.3.3.5.2.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.