SJC Home
Clearance Sheet C2020-004494*002

 Department IssuesSigned OffIntl

Plan reviewed for Revision to approved plans. Revision Added fans, move heaters. Sheets included for review are A-3, P-2.1, P-5, P-7

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

RESUBMITTING:
A. Make necessary changes and resubmit everything in person to the Permit Center.
B. Once at the Permit Center swap out altered pages or insert new pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.
C. Provide a response to comments along with any supporting documentation.  Response to comments is REQUIRED not optional.
- The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8".
- Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)

 

1) Revision states "added fans. I only see where one fan was moved and one fan was deleted, both in the outside dining.

Identify all fans that were affected by the revision. I.E., "deleted one fan and moved one fan in the outside dining area" for example.

 

2) The fans shown are not the same style of fans shown in the original plans. These appear to be wall type. The plans also state "See mechanical drawings for heaters.

Provide the missing mechanical sheets (and electrical) showing the heater information.

 

3) I found that one fan had been deleted and one fan move in the outside dinging. The revision sheet stated "added fans". I do not see any new fans, only deleted and moved fans in the outside dining.

Provide the missing electrical sheets showing the updated information on the fans.

 

4) Not enough information on the changes made in this revision. Provide detailed information on what is changed, added, removed, relocated, etc. For example: removed emergency lights - see sheet E-2 exhibit 2A. Fore Example.