SJC Home
Clearance Sheet C2020-004494*002

 Department IssuesSigned OffIntl

Plan for an Ansul R102 6 gal kitchen suppression system for 2, 9' abutted hoods.  The system utilizes 19 out of 22 available flow points. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

1/12/2022 PWebb