| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for interior build out of shell. 5,300 SF Type IIB construction, Sprinkled, No fire alarm, Assembly - Restaurant.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Tuesday, October 19, 2021 DF: Review of 1st resubmittal. Revised pages G-2, A-1, A-1.6, A-3, A-4.2, E-2, E-5 and E-7 submitted loose and not swapped out of the plan set.
NOTE: THESE SHEETS ARE TO BE INSERTED INTO THE PLANS AND THE OLD ONES REMOVED.
|
10/20/2021
| dfeagle |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
10/20/2021
| dfeagle |
|
|
1) Exit signs must match BOTH Electrical page(s) and Life Safety Code page(s).
|
10/19/2021
| dfeagle |
|
|
2) Sheet A-1 indicates the used cooking oil will be stored outside by the dumpster(s) in a tank approx. 200 gallon capacity.
Provide a St Johns County Fire Marshals Above Ground Tank Permit. Show compliance with NFPA 1 Chapter 66 (1:66.9.19, 1:66.21) for a combustible IIIB liquid.
Tuesday, October 19, 2021 DF: Response: The tank shown below will be in compliance with the NFPA requirements. It comes equipped with a locking lid.
|
10/20/2021
| dfeagle |
|
|
3) Sheet A-1.4 indicates a large CO2 tank outside the building. Will CO2 beverage system exceed 100 pounds? If so, demonstrate compliance with NFPA 55:13.10.
NOTE: Make sure to include CO2 tank location, CO2 piping to mixing location (ex- bag/box), indicate which option will be used (ventilation vs sensor/notification) AND show compliance with chosen option of compliance. If Sensor/notification, show locations of the devices.
Tuesday, October 19, 2021 DF: Response: The CO2 tank is located outside the building and does exceed 100 lbs. Sensors and notification devices will be provided at the bag-n-box location.
Tuesday, October 19, 2021 DF: Reviewers Response: A revision to the construction permit will need to be provided showing the CO2 system layout, locations of the annunciator(s) - (at lease one in the occupied space outside of the hazard area, sensor(s), warning devices (audible and visual), Manufacturers spec sheets on the devices, etc.
A 109 Insulation HOLD has been placed on the permit for the revision.
|
10/20/2021
| dfeagle |
|
|
4) Sheet A-4.2: Door 102's hardware noted as "Existing Door & Hardware To Remain".
Provide the door hardware for this double door set. This This double door set requires panic hardware. 101:12.2.2.2.3.
NOTE: 101:12.2.2.2.4 is only permitted on the main exit single or single pair of doors
Tuesday, October 19, 2021 DF: Response: Door 102 will be equipped with panic hardware.
Tuesday, October 19, 2021 DF: Reviewers Response: The door and hardware schedule on sheet A-4.2 was not updated to reflect the change. NOTE: Both doors are required to have panic hardware on each door. 12.2.2.2.3. Options such as automatic flush bolts may apply. Should you decide to use automatic flush bolts you will need to submit the flush bolts spec sheets for review.
Provide an updated door and hardware schedule to reflect the panic hardware.
A 109 Hold (Insulation) has been placed for the revision for the hardware.
|
10/20/2021
| dfeagle |
|
|
5) No Illumination of means of egress noted for the outside dining area and through to the end of the planter. 101:12.2.8
If the original shell is providing this lighting or the lighting is new/changed with this build out, show the lighting on the plans and note it as necessary for clarity.
Tuesday, October 19, 2021 DF: Response: Emergency lights have been added at the outdoor seating area.
|
10/20/2021
| dfeagle |
|
|
6) Emergency lighting: No emergency lighting noted in the outdoor dining area, outside all exit doors and inside the bar. No manufacturer make / model or manufacturers specification sheet provided to determine if the placement of the emergency lighting meets the manufacturers installation requirement to meet NFPA 101:7.9
Some of the EL's are on the walls over racks, equipment which detracts from the covered egress path. It has been my experience that with today's technology emergency lighting coverage varies greatly. Even with new technology, most EL's only cover a 3' or 6' wide egress path from the wall/location mounted and depending on manufacturer/model, only 8' to each side.
a) Provide the manufacturers specification documentation so I can verify coverage. OR,
b) Provide photometrics demonstrating the EL's coverage complies with 101:7.9.2.1.1
NOTE: Not all Wall type EL's are listed for ceiling mount. If the EL's are to be mounted on the ceiling, provide the ceiling height.
Tuesday, October 19, 2021 DF: Response: See photometric calculations for emergency egress lighting on sheet E-7.
|
10/20/2021
| dfeagle |
|
|
7) Additional exit signs appear to be needed in the dining room to guide the patrons to the rear exit. 101:7.10.1.2.2
|
10/19/2021
| dfeagle |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- 109 Hold (Insulation) for revision to door 102's hardware - Fire sprinkler system - 109 Hold (Insulation) for revision for CO2 alarm - Kitchen hood - Kitchen suppression system - -
|
10/20/2021
| dfeagle |