1) The foundation plan does not address the interior load bearing walls per the truss lay-out ( 2- copies required )

9/28/2020 jadams

2) The electrical plans need to address occupancy sensors per FBC Energy Conservation C405.2.1 , Identify location of meter and panels on plans.  

9/28/2020 jadams

3) provide a plumbing plan with riser diagram

9/28/2020 jadams

4) Provide a mechanical plan showing location of equipment ,duct size and lay-out , and ventilation   

9/28/2020 jadams

5) no attic access shown ( is this going to be used for storage )

9/28/2020 jadams

6) Page A-4 does not address ceiling insulation

9/28/2020 jadams

7) how are the ceiling trusses attached to the metal building

9/28/2020 jadams

8) Elevation plans are required ( front  ,sides and rear )

9/28/2020 jadams