Plan submitted for a new Ansual R102 system (9gal. 22 flow pt avail, 10 flow used) to protect a 12' hood covering L to R: 36"x24" charbroiler, 40"x40" oven, and 48"x24" range.. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer:
V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Friday, April 30, 2021 Plan updated for new ansual R102 system (9gal, 22 flow point aval, 13 flow used) to protect L to R: 14x14 fryer, 36x24 charbroiler, 40x40 oven and 48x24 range.