Clearance Sheet C2020-003926*002

 Department IssuesSigned OffIntl

Plan is a revision to sheet T-1 for a NuCO2 brand Co2 monitoring system/alarm for a new restaurant.  The plans show the control unit located in a storage room with sensors in 2 restrooms and the kitchen area.  The plans do not show the CO2 tank location and pipe routing, however Supervisor Gedris is familiar with the project and indicated that the lines are ran above the ceiling where the sensors are and the locations are appropriate.  The plan is APPROVED with important note below. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

2/11/2021 PWebb

Important Note:

The control unit needs to be located in a normally occupied space ie/the hallway.  Do not install it in the indicated storage room.  The storage room does need a sensor though.  This will be verified at the time of final. 

2/11/2021 PWebb