SJC Home
Clearance Sheet C2020-003926*002

 Department IssuesSigned OffIntl

Plan reviewed for build out of new 2535sf assembly in an existing construction type IIb sprinklered shell building separated from adjacent space by 1 hr wall. Reviewed as new assembly using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

NOTE: Based my review on 99p since occ load calculated incorrectly (101:12.1.7.1).

1/7/2021 agedris

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

1/7/2021 agedris

1) Indicate the capacity of your beverage CO2 system on the plans.  If the system exceeds 100 pounds of product, demonstrate compliance with NFPA 1:63.3.1.2.4.1 on the plans. 

Monday, January 4, 2021 Page P3 swapped out. Plans now show bollards but nothing to address 1:63.3.1.2.4.1.

Thursday, January 07, 2021 Contractor dropped off an updated E3 page. Updated page contained note to address compliance with above reference. plans showed location of CO2 monitoring control system however no sensor locations were indicated. addressed this with Lance Mariotti and he advised he would submit a revised E3 page showing the location of sensors and the specific make and model of system. A HOLD will be placed at 105 framing for revised E3 page and CO2 monitor spec sheets. AGEDRIS Thursday, January 07, 2021

1/7/2021 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:


- fire sprinkler system (FP1 Alonzo Myler)
- kitchen hood (shown on T1)
- kitchen suppression system (to cover eq. under hood on T1)

12/2/2020 VVitori

2) Wall packs provided for emergency lighting not providing coverage for exit path. The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path.  Provide emergency illumination along the exit path. 101:7.9.2

***With my experience, a typical wall pack emergency light usually mounted 8' above the floor covers approx. 8' either direction with a 3' wide path.***

Monday, January 4, 2021 Page E2 shows additional emergency lights.

1/4/2021 VVitori

If gas piping out back is subject to vehicular damage protect it in accord with 1:60.5.1.9.2.  Required by 1:63.3.1.9.4

12/2/2020 VVitori

Page E2 kitchen area indicates that motion sensors will be used in the areas of egress. At time of fire final be prepared to show compliance with NFPA 101 7.8.1.2.2:

(1) switch controllers must be listed (2) switch controllers equipped for fail-safe operation and evaluated for this purpose (3)  timers be set for a minimum 15 minute duration. (4)  motion sensor be activated by any occupant movement in the area served by lighting units (5) If building has a fire alarm, activation of fire alarm must activate the switch controller (6)  lighting control device may not turn off any lights realized upon for activation of photo luminescent exit signs or path markers (7) Lighting control devices may not turn off any battery equipped emergency luminaries, unit equipment or exit signs

12/2/2020 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish will meet Class A, B or C. 101:12.3.3.3

- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:12.3.3.5.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

12/2/2020 VVitori