Plan APPROVED for fire main for overall site, Kennel Staff/Training, Kennel B, Kennel C, Quarantine Kennel, and Food Storage building.
Scope begins 8" DCDA backflow, 530 ft (+/-) 8" DR-18 to supply two private RED fire hydrants; 425 ft (+/-) 6" DR-18 to supply fire risers 1' AFF for Kennel Staff/Training, Kennels B, C, and Quarantine Kennels; 130 ft (+/-) 4" DR-18 to supply fire riser 1' AFF for Food Storage building also
Stub outs to Kennels A, and D, Vet Clinic, K-9 Training and Admin buildings. (These 5 buildings required separate underground fire main permit to finish to risers).
Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: S. Murray 904-209-1742
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.