SJC Home
Clearance Sheet C2020-003599*007

 Department IssuesSigned OffIntl

Plan REJECTED for fire main for overall site, Kennel Staff/Training, Kennel B, Kennel C, Quarantine Kennel, and Food Storage building. 

Scope begins 8" DCDA backflow, 530 ft (+/-) 8" DR-18 to supply two private RED fire hydrants;  425 ft (+/-) 6" DR-18 to supply fire risers 1' AFF for Kennel Staff/Training, Kennels B, C, and Quarantine Kennels; stub outs to Kennels A, and D, Vet Clinic, K-9 Training and Admin buildings. (These 5 buildings required separate underground fire main permit to finish to risers);  130 ft (+/-) 4" DR-18 to supply fire riser 1' AFF for Food Storage building.

Reviewed using FFPC 7th edition effective January 1, 2021.

Reviewer: S. Murray 904-209-1742
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

1. Regarding the backflow preventer, it is noted it will be freeze protected. The backflow is required to be electronically supervised per EOR of sprinkler on page FP1.1 and required by 101:42.2.4.1 101:42.2.5  101:38.2.5.2.1  101:38.2.5.3.1. Please acknowledge accommodation for monitoring the backflow will be made for the fire alarm contractor.

 

2. Regarding Fire Dept Connections for all the buildings, they are required to be freestanding out by the road. This was mentioned during the civil review. Additional the EOR of fire sprinkler system states remote freestanding FDCs to be installed off dedicated fire riser check valve and downstream of fire riser check valve in accordance with NFPA 13. Please provide updated utility plans showing the freestanding FDCs by the road including size of pipe.

 

3. FDC connections on piping LARGER than 2 inches shall be equipped with a five (5) inch Storz connection and shall have a 30 degree downward deflection. (NFPA 24:5.9.1.2, and 5.9.2.4) Please provide submittal sheets for the Storz FDCs.

 
Informational

**Fire Dept Connection shall:
- 36" clearance in front and side of FDC
- Have check valve (NFPA 13)
- Have caps in place. (NFPA 24 5.9.1)
- Labeled as to which building is serves by either the address or building name. (NFPA 24 5.9.5)  
  

 
Informational

**General Requirements:
- Top of the pipe shall be buried not less than 2 1/2 ft to prevent mechanical damage (NFPA 24:10.4.2.2.2)
- Pipe under driveways shall be buried at a minimum depth of 3 ft (NFPA 24:10.4.2.2.3)

 
Informational

**To schedule a fire inspection BEFORE cover up of pipe, use the automated system: please call 904-827-6842 press 1, enter building permit _____ and enter appropriate code for sprinkler underground visual(638), sprinkler underground hydro(605), sprinkler underground flush(637)
OR call 904-209-1740 press 1, then press 2.

INFORMATIONAL: Your permit fee includes the cost of review, one hydrostatic test inspection and one final inspection. If you will require more than one hydro/visual inspection you will need to call 209-1740 x 1 to arrange payment.