| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for 89 total devices between all 5 buildings. This fire alarm permit will only cover the 18 devices in Building 1 Kennel / Staff Training. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
|
1) Do not see audible and visual exterior alarm. 150:9.3.2
|
| |
|
|
2) Do not see where backflow is electronically supervised. EOR of sprinkler on required this on FP1.1 and required by 101:42.2.4.1 101:42.2.5 101:38.2.5.2.1 101:38.2.5.3.1.
|
| |
|
|
3) Do see where standard illumination of lighting sensors will be tied in to illuminate egress when alarm activates. 101:7.8.1.2.2
|
| |
|
|
4) This building has access controlled egress which is required to release with fire alarm activation. Show these doors being tied in for release. 101:38.2.2.2.6 101:42.2.2.2.3
|
| |
|
|
5) Update fire alarm permit application with correct number of devices for this building.
|
| |