| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for 64 heads NFPA 13 sprinkler system. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
NOTE: no spec sheets provided for flex heads, Sin RA7216
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
|
1) No sprinkler or site underground permit applicant and plans has been submitted yet. Have underground contractor submit.
|
| |
|
|
2) Page received is FP2 (only head layout). Is this the only page? Is there and FP1? Where is riser elevation? Where is inspectors test? Where is the FDC? No building elevation.
A complete review can not be conducted.
|
| |
|
|
3) FP2 shows flex assembly heads will be used. Provide spec sheet for suspended ceiling tile grid showing it meets ASTM C 635. 13:9.2.1.3.3.2
|
| |
|
|
4) How will piping in attic be protected against freezing?
|
| |
|
|
5) Hydraulic calculations for southeast corner of kennel remote area 2 indicates area of application is 1592sf. EOR on FP1.1 indicates 1500sf over most remote area for kennel remote area.
|
| |