| | Department Issues | Signed Off | Intl |
|
|
This review covers "Building 1" (Kennels A, B, C, D, Staff and Training).
Plan reviewed for 22727sf construction type VB fire sprinklered (5 separate sprinkler risers) and fire alarmed 2 story business building. Submitted as storage of Class 2 Catergory B animal housing. 5 separate buildings attached via a metal covered walk way. Reviewed as new mixed use animal housing storage and business using FFPC 6th edition (including NFPA 150) effective Dec. 31, 2017.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
NOTE: 1 set of plans for 4 separate clearance sheets: C20-1810 22727sf kennel Building 1, C20-1811 4284sf Vet Building 2, C20-1812 3198sf Quarantine Kennel Building 3, C20-1813 948sf Food Storage building 4.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
|
1) This is a preliminary review. Do not resubmit until clearance sheet obtained.
NOTE: Based on fire's site review, additional comments may be provided.
|
| |
|
|
2) Since one pair of plans submitted for 4 separate clearance sheets, this comment will be signed off once all clearance sheets have all fire plan review comments addressed.
C20-1810 22727sf kennel Building 1, C20-1811 4284sf Vet Building 2, C20-1812 3198sf Quarantine Kennel Building 3, C20-1813 948sf Food Storage building 4.
|
| |
|
|
3) Plan page LS0.1 shows this building as 22727sf. Comm20-13 site plan page 3 showed this/these buildings (kennel A, B, C, D, Staff and training) as only 16907sf. Update which ever plan is not correct.
|
| |
|
|
4) Are these considered 1 building or 5 separate buildings according to Florida Building Code? If considered 1 building, update design to meet 150:7.2 (increase building construction type, decrease building square footage OR create more than one building).
|
| |
|
|
5) This building was design as business occupancy only. Identify occupancy of first floor (mixed or separated storage?). Update code summary to update occupancy of building.
Storage Occupancy - An occupancy used primarily for the storage or sheltering of goods, merchandise, products, vehicles, or animals. 1:6.1.13.1 or 150:A.11.1.1
|
| |
|
|
6) Illustrated occupant load on LS0.4 of 2nd floor is shown as 5p for 621sf. Update occupant load of second floor to comply with 101:38.1.7 (101:7.3.1.2).
|
| |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system: - fire alarm system (tie in of: backflow supervision 101:42.2.4.1 101:42.2.5 101:38.2.5.2.1 101:38.2.5.3.1, access controlled egress 101:38.2.2.2.6 101:42.2.2.2.3, standard lighting motion sensors 101:7.8.1.2.2, monitored 150:9.2.4 - fire sprinkler system - fire underground
|
| |
|
|
7) The following is unaddressed or missing from fire alarm design criteria (E2.4, E5.2, E5.3, E5.4 EOR Thomas Elder) as required by 61G15-32.008:
a) general occupancy for this building.
b) does not address connections to related systems (at minimum: access control doors, motion sensors, audible and visual exterior alarm 150:9.3.2)
e) matrix does not address access control doors, motion sensors
Will this be 1 alarm for all 5 sections or 5 separate alarms for each of the 5 risers?
|
| |
|
|
Page E1.1a and E1.2 indicates that motion sensors will be used in the areas of egress. At time of fire final be prepared to show compliance with NFPA 101 7.8.1.2.2:
(1) switch controllers must be listed (2) switch controllers equipped for fail-safe operation and evaluated for this purpose (3) timers be set for a minimum 15 minute duration. (4) motion sensor be activated by any occupant movement in the area served by lighting units (5) If building has a fire alarm, activation of fire alarm must activate the switch controller (6) lighting control device may not turn off any lights realized upon for activation of photo luminescent exit signs or path markers (7) Lighting control devices may not turn off any battery equipped emergency luminaries, unit equipment or exit signs
|
| |
|
|
At least 1 2-A:10-B:C extinguisher shall be provided. 150:9.4.2
|
| |
|
|
Page E0.2 calls for lightening protection. At this time the fire department will not review or inspect this type of system. This office requires a 3rd party inspection. Remember installation is required to meet NFPA 780 and UL 96A. The installing contractor will be required to provide certification to the fire inspector at the time of fire final indicating compliance with NFPA 780 and UL96A was met.
|
| |
|
|
Plan page LS0.3 and LS.5 shows a rapid entry box going on the building. Our department utilizes FAIL SAFE. The required box for this jurisdiction is the "LBI FAIL- SAFE- LOCK BOX WITH TAMPER SWITCH". Contact St Johns County Fire Rescue Secretary Dawn Lyons at 904-209-1712 for the correct order form.
Several doors throughout the property have access controlled egress doors (shown on A2.4 and A8.2) AND electronically controlled egress doors (shown on LS0.4). You will need to provide all keys, codes and/or swipe cards to be placed in Fail Safe box.
|
| |
|
|
8) The following is unaddressed or missing from sprinkler design criteria (FP1.1 Thomas Elder) as required by 61G15-32.004:
d) temperature ratings not called out
g) EOR indicates property may use 1 of 4 options allowed in 13:8.16.1.1.2 to monitor backflow. It is required to be electronically monitored by 101:42.2.4.1, 101:38.2.5.2.1 , and 101:38.2.5.3.1.
h) EOR identifies MIC as an issue but does not address corrective measures other than monitor the issue. What action needs to be taken to address the MIC?
i) what is max allowable pressure drop?
m) provide owners certificate
|
| |
|
|
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- wall and ceiling finish will meet Class A, B or C. 101:42.3.3.2 101:38.3.3.2.2 150:10.1.1.2
- wall and ceiling finish in exits and exit access corridors. 101:38.3.3.2.1 101:10.1.1.1
- floor finish shall meet Class I or II in exit enclosures and exit access corridors. 101:42.3.3.3.1 101:38.3.3.3.2
- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:38.3.3.3.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.
|
| |
|
|
9) Provide manufacturer spec sheet for intumescent paint that satisfies the 1hour separation at 2nd story floor shown on pages A4.5 and A4.6.
|
| |
|
|
10) Do not see where food prep/feed room is fire separated. 150:7.6
|
| |