| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for 89 total devices between all 5 buildings. This fire alarm permit will only cover the 5 devices in Food storage building. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
1) Do not see audible and visual exterior alarm. 150:9.3.2
|
| |
|
|
2) Do not see where backflow is electronically supervised. EOR of sprinkler on required this on FP1.1 and required by 101:42.2.4.1 101:42.2.5 101:38.2.5.2.1 101:38.2.5.3.1.
|
| |
|
|
3) Submit fire alarm permit application for each building.
|
| |
|
|
4) Do not see location of controls and annunciation is provided in this building. 101:9.6.6 and 101:9.6.7.7
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |