Clearance Sheet C2020-003599*005

 Department IssuesSigned OffIntl

#1

 need signed / approved clearance sheet with attached site plan

3/9/2021 jadams

#2

need eng. truss drawings with eor review stamp

 

3/9/2021 jadams

#3

sheet ls0.1 lists bldg.#3 as 2971 sq ft + 622 = 3593 / application lists 3198

3/9/2021 jadams

#4

per nec 110.24 service equipment shall be marked with the max. fault current available

3/9/2021 jadams

#5 all elec panels need designated areas they serve / control marked

3/9/2021 jadams

#6

per fmc 401.6 contaminants cannot be recirculated

3/9/2021 jadams

INFORMATION Hold on slab inspection for EOR approved truss package