Clearance Sheet C2020-003599*001

 Department IssuesSigned OffIntl

Issues Report For FIRE

Fax Copy
Clearance Sheet: C2020-003599*007
Project Name: K9s For Warriors (Building 1)
Project Address: 80 WARRIOR WAY
Contractor: MARTY, NATHANIEL T

DEPARTMENTS:

FIRE SERVICES

Reviewed By : STEPHANIE MURRAY 823-2709


Issued: 11/4/2021 11:12:58 AM

Plan APPROVED for fire main for overall site, Kennel Staff/Training, Kennel B, Kennel C, Quarantine Kennel, and Food Storage building. 

Scope begins 8" DCDA backflow, 530 ft (+/-) 8" DR-18 to supply two private RED fire hydrants;  425 ft (+/-) 6" DR-18 to supply fire risers 1' AFF for Kennel Staff/Training, Kennels B, C, and Quarantine Kennels; 130 ft (+/-) 4" DR-18 to supply fire riser 1' AFF for Food Storage building also

Stub outs to Kennels A, and D, Vet Clinic, K-9 Training and Admin buildings. (These 5 buildings required separate underground fire main permit to finish to risers). 

Reviewed using FFPC 7th edition effective January 1, 2021.

Reviewer: S. Murray 904-209-1742
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.


Sign Off: 11/4/2021 12:38:38 PM SMurray



Issued: 11/4/2021 11:17:06 AM

Fire Dept Connections are freestanding in front of each building with 5" storz connection. They shall have:
- 36" clearance in front and side of FDC
- Have check valve (NFPA 13)
- Have caps in place. (NFPA 24 5.9.1)
- Labeled as to which building is serves by either the address or building name. (NFPA 24 5.9.5)  


Sign Off: 11/4/2021 12:38:36 PM SMurray



Issued: 11/4/2021 11:20:09 AM

Backflow preventer will be freeze protected and be electronically supervised per EOR of sprinkler on page FP1.1 and required by 101:42.2.4.1 101:42.2.5  101:38.2.5.2.1  101:38.2.5.3.1. Please provide accommodation for monitoring the backflow for the fire alarm contractor.


Sign Off: 11/4/2021 12:38:35 PM SMurray



Issued: 11/4/2021 11:21:38 AM

To schedule a fire inspection BEFORE cover up of pipe, use the automated system: please call 904-827-6842 press 1, enter building permit _____ and enter appropriate code for sprinkler underground visual(638), sprinkler underground hydro(605), sprinkler underground flush(637)
OR call 904-209-1740 press 1, then press 2.

80 warrior-12109545, 70 warrior-12109551, 90 warrior-12109556, 71 warrior-12109560, 120 warrior-12109558

INFORMATIONAL: Your permit fee includes the cost of review, one hydrostatic test inspection and one final inspection for EACH building. If you will require more than one hydro/visual inspection you will need to call 209-1740 x 1 to arrange payment.  


Sign Off: 11/4/2021 12:38:34 PM SMurray