| Department Issues | Signed Off | Intl |
|
Plan submitted for BDA system in new building. Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
1) Do not see where building will be provided with NFPA 780 lightning protection. Main building plans need electrical revision showing building will be protected with NFPA 780 lightning protection. 1221:9.6.3
|
| |
|
2) Unable to locate where all repeater, transmitter, receiver, signal booster components, external filters and battery system components will be put in a nema4- or nema4x type enclosure. 1221:9.6.11.2
|
| |
|
Make sure primary power source is supplied from dedicated branch circuit. 1221:9.6.12.1
|
| |
|
3) Where is the dedicated panel to be located? 1221:9.6.13.2
|
| |
|
4) Where is all of 1221:9.6.14 information provided?
|
| |