Plan reviewed for new FM200 system to cover IT computer room. Reviewed using FFPC 7th edition effective January 1, 2021.Reviewer: V.Vitori 904 209 1748 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Make sure manual operating device is easily identified as to the hazard it protects. 2001:4.3.3.10
Make sure warning and instruction signs posted at entrance to and inside protected area. 2001:4.3.5.5
Installation approval will need to meet 2001:7.7
Currently abort switch is shown outside of the protected area. 2001:4.3.5.3 requires it to be located within the protected area near the means of egress.