Plan reviewed for revision to 40 of 76 original pages (cover, A1.01,A2.01, A2.1, A2.11, A2.12, A2.51, A3.01, A4.51, A5.01, A5.51, A5.52, A5.53, A6.01, A6.02, A6.03, A6.04, A8.01, A8.02, S1.01, S1.02, S1.03, S2.02, S3.01, S5.02, S6.02, S6.03, S7.01, M1.01, M1.02, E0.01, E.02, E0.03, E0.05, E1.00, E2.01, E2.02, E3.01, E3.02, E3.03). Scope of changes: "value engineering changes". Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer:
V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
NOTE: Any site changes need to go back through site review.
Page E0.05 shows FM200 fire suppression system being added according to FA design criteria.