Plans for a revision to the previously approved kitchen suppression plan. The previously approved plan indicated a Denlar D1000 hood and suppression system that discharged through the roof. The revision is to change it from the roof discharge to the front discharge/recirculating system. Per the contractor the system installed is the Denlar D1000 series model D1030-F. This model does permit this. The Revision is APPROVED.
Reviewed using FFPC 7th edition effective Dec. 31, 2020.