Plans for the installation of a Denlar Residential hood and fire suppression system that is vented outside through the roof. The system is protecting a Samsung Residential Stove. The plans are APPROVED as submitted in accordance with NFPA 1:50.1.4.
Note to Contractor: Ensure that a 4A extinguisher is provided within 75 feet of the break room.
Note to inspector: The hood and suppression are integrated into the same system, no hood permit required.
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.