Clearance Sheet C2019-006879

 Department IssuesSigned OffIntl

Plan reviewed for aboveground only new 111 head NFPA 13 sprinkler system in a new assembly. Reviewed using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

3/25/2020 VVitori

Note located left side on plan pageFP1 reads "Exposed pipe insulated by others". This insulation must be installed prior to sprinkler final.

3/25/2020 VVitori