At the time of fire final be prepared to provide a copy of manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- wall and ceiling finishes meet Class A and B in the lobby. 101:12.3.3.2
- wall and ceiling finishes meet Class A, B or C other than in the lobby. 101:12.3.3.3
- floor finishes meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:12.3.3.5.3
- combustible scenery of cloth, film, vegetation, fabrics and similar materials shall meet NFPA 701 OR have a heat release that does not exceeding 100kW when tested in accordance with NFPA 289. 101:12.4.6.11.1 101:12.7.4
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.