Plan reviewed for Duct Smoke Detector tie in to the buildings Fire Alarm System.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

4/26/2021 dfeagle

NOTE: The Keyed Remote Test Stations are to be in a location that is normally occupied such as the front lobby, receptionist desk, hallway, etc. where the visual/audible notification will be noticed while the building/unit is occupied. for example. Inside an office, storage room, bathroom, etc. is not an approved location. 

The visual / audible signal is to be located in such a manner that no ladder, step stool or extension device is required to visually view or operate the notification device.

Monday, April 26, 2021 4:32:04 PM DF: Spoke with Cheryl Gates 904-388-1700 regarding the location of the keyed remote test stations. Cheryl agreed t move the one station from the office.

4/26/2021 dfeagle