Clearance Sheet C2019-006720*004

 Department IssuesSigned OffIntl

Plan reviewed for a 3,900 SF buildout for a class B mercantile. Type IIB construction unprotected, sprinkled.

Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Plans are APPROVED.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

Wednesday, March 3, 2021 DF: Plans resubmittal addressing Building Plan S Comments. Pages replaced are Project Page and pages E1, E2, E3, and E4.

Plans are APPROVED.

Reviewer: D. Feagle 904-209-1721

3/3/2021 dfeagle

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

2/1/2021 dfeagle

1) Emergency lighting. 101:36.2.9

a) No emergency lighting shown in bathrooms 106 and 107. Add emergency lighting in these two rooms.

Monday, February 1, 2021 0945hrs. DF: Spoke with Stacey Steinfeld with Lawrence Group regarding the missing emergency lighting in the bathrooms. Per Ms. Steinfeld they will have the emergency lighting installed and understand the Fire Inspector will verify compliance at time of the Fire Final.

Wednesday, March 3, 2021 DF: Plans now show emergency lighting in the bathrooms.

3/3/2021 dfeagle