SJC Home
Clearance Sheet C2019-006513

 Department IssuesSigned OffIntl

Plan reviewed for new 6255sf mixed use day care and education in an construction type Vb fire sprinklered building. Reviewed as new mixed use day care and education using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
Victoria Vitori 904 209 1748
Anthony Gedris 904-209-1741

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

RESUBMITTING:  Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) Do not resubmit until clearance sheet acquired.

Reminder for reviewer: don't forget to add holds, check approved fire site comments, check location of fdc.

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until a permit has been pulled :
- fire alarm system (EOR Kenneth W Hunter E2.2 and E3.0)
- fire sprinkler system (EOR Matthew D Lewis FP0.1, FP1.1, FP1.2 includes attic)
- fire underground

 

2) Fire alarm design criteria is not complete. The A-O of 61g15-32.008 is to be submitted with the general construction documents. Point out the missing information on the signed and sealed pages from Fire Alarm EOR Kenethh W Hunter. Missing or incomplete fire alarm design criteria items: a, b, c, e, f, g, h, I, o

Make sure all shut off valves on sprinkler supervised (including the backflow). This should be addressed under b. 101:14.3.6  101:14.2.11.1.2  101:16.2.11.1.2(1)  101:16.3.6(2)

 

3) Occupant load for activity room calculated at 50sfpp. This space also needs to be calculated using maximum probable population (101:14.1.7.1  101:16.1.7.1). If this intends to be used as an assembly also (lunch, events, graduation, parties...) calculate using 101:7.3.1.2.

Make sure any items triggered by an increase in occupant load will be addressed also.

 

At the time of fire final be prepared to provide a copy of manufacturer specification sheets to the fire inspector showing that each  finish will meet:

- wall and ceiling finish in corridor must meet class A. 101:16.3.3.2

- wall and ceiling finish other than corridors must meet class A or B 101:14.3.3.2  101:16.3.3.2

- floor finish in exit access corridors must meet Class I or II. 101:14.3.3.3.2  101:16.3.3.2

- floor finish other than in exit access corridors - either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:14.3.3.3.3  101:16.3.3.3

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

 

4) Unable to locate which corridor doors will be self closing or automatic closing. 101:14.3.6(2)  101:16.3.6(2)

 

5) Do not see that laundry is fire separated from remainder of the building. 101:14.3.2.1(2)(a)

NOTE: Do not forget to up date door page showing door(s) will be fire rated with self closer. Not sure how a sliding door will meet all fire door requirements.