SJC Home
Clearance Sheet C2019-005916

 Department IssuesSigned OffIntl

Plan reviewed for new 2,376.56 square feet mini storage building. Reviewed as new storage using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

NOTE: Plans included a check (#1235) for 513.90. The check is attached to the plans cover sheet. Left check with the set of plans (C19-5916).

*****************

Wednesday, June 10, 2020  Resubmittal included page A1 (including LSP), stapled pages including E0.1, E1.1, E2.1E2.2, E3.1, E3.2, E3.3, M0.1, M2.1, M2.2, and M7.1.

Code analysis on page A1 now identifies the building SF as 2,468.

Plan review for 1st resubmittal. Page A1 submitted includes Life Safety Plan and code analysis.
6/18/2020 agedris

RESUBMITTING:  Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

6/18/2020 agedris

1)  Provide a complete code analysis for this project. NFPA 1: 1.7.12 Please illustrate occupancy type and compliance with the adopted edition of the Florida Fire Prevention Code. Contact an Architect to illustrate Code compliance.

Example of items that need to be addressed: Code and editions, Occupancy of structure/project, fire protection system(s) if included, exit sizes, exit numbers, extinguishers, emergency lights, exit signage, address, light weight truss, what will be in there or processes could present other requirements.  

**************************

Wednesday, June 10, 2020  Code analysis provide on resubmittal page A1.

Informational only - No Response Needed. Noted the 5th edition of the Florida Fire Prevention Code (FFPC). Current edition of the FFPC is the 6th edition.

6/10/2020 dfeagle

2)  Missing the following pages: Life Safety, Mechanical, Electrical, Plumbing

****************

Wednesday, June 10, 2020

The electrical and mechanical pages identify electrical pages for buildings A, B, D, E1 and E2. The electrical page (E2.1) for building  A  contains the wrong building/corridor layout.

a) Remove ALL buildings, building comments, and pages not related to building A.

b) Remove building “B” from page E2.1 and correct building A’s building layout.

6/18/2020 agedris

3)  Plans do not indicate illumination of means of egress for the interior corridor. NFPA 101:42.2.8

*********************

Wednesday, June 10, 2020    The electrical page for building A (E2.1) contains the wrong building/corridor layout. I am not able to verify illumination of means of egress based on the wrong building layout.

Remove building “B” from page E2.1, correct building A’s building layout and identify the illumination of the means of egress.

6/18/2020 agedris

4)  Plans do not indicate Emergency lighting of means of egress for the interior corridor.

Provide the specification sheets and any photometrics for the emergency lights that you are proposing for the building so I can verify coverage. NFPA 101:42.2.9

*********************

Wednesday, June 10, 2020    The resubmittal electrical page for building A (E2.1) contains the wrong building/corridor layout. I am not able to verify emergency light coverage of means of egress based on the wrong building layout. No specification sheets were provided.

a) Remove building “B” from page E2.1, correct building A’s building layout and identify the emergency lighting of the means of egress.

b) Provide specification sheets for the emergency lighting to be installed. The emergency lighting on page E2.1 show they are 39 feet apart.

NOTE: Most wall packs are listed for a mounting height of 7.5 feet with spacing between devices of around 10 feet, while providing the required illumination to between 3 to 6 feet from the wall.

6/18/2020 agedris

5)  Need additional exit sign at the end of the long corridor where it turns to the short corridor’s exit door. Include the direction arrow to the exit door. NFPA 101:7.10.2.1

*********************

Wednesday, June 10, 2020    The resubmittal electrical page for building A (E2.1) contains the wrong building/corridor layout. I am not able to verify exit sign coverage for the change of egress direction based on the wrong building layout.

Remove building “B” from page E2.1, correct building A’s building layout and identify the exit signage in the means of egress.

6/18/2020 agedris

6)  Exit signs must match BOTH Electrical page(s) and Life Safety Code page(s).

NOTE: Both Life Safety pages and Electrical pages must match for the emergency lighting and exit signage. 

*********************

Wednesday, June 10, 2020    The resubmittal electrical page for building A (E2.1) contains the wrong building/corridor layout and does not match the LSP layout on page A1.

Remove building “B” from page E2.1, correct building A’s building layout and match the exit signage on the LSP page A1 with building A's electrical page.

6/18/2020 agedris

7)  The two corridor egress doors (rollup doors) do not meet NFPA 101:42.2.2.2.1, 101:7.2.1.

Provide doors meeting NFPA 101:7.2.1. Any latching / locking hardware shall be in compliance with NFPA 101:7.2.1.5

*********************

Wednesday, June 10, 2020    The resubmittal electrical page for building A (E2.1) contains the wrong building/corridor layout. No door or hardware schedules provided.

a) Provide the door and door hardware schedules.

6/18/2020 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

NOTE:  After the review of any resubmittal, additional review comments may be added.

6/18/2020 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:
- failure of a public utility or other outside electrical power supply
- opening of a circuit breaker or fuse
- manual act(s), including accidental opening of a switch controlling normal lighting facilities. NFPA 101 7.9.2.3

6/18/2020 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

Wednesday, June 10, 2020  Automatic lighting controls were noted on the resubmittal electrical pages.

NFPA 101: 7.8.1.2.2  
Unless prohibited by Chapters 11 through 43, automatic lighting control devices shall be permitted to temporarily turn off the illumination within the means of egress, provided that each lighting control device complies with all of the following:
(1) In new installations, the lighting control device is listed.
(2) The lighting control device is equipped to automatically energize the controlled lights upon loss of normal power and is evaluated for this purpose.
(3) Illumination timers are provided and are set for a minimum 15-minute duration.
(4) The lighting control device is activated by any occupant movement in the area served by the lighting units.
(5) In new installations, the lighting control device is activated by activation of the building fire alarm system, if provided.
(6) The lighting control device does not turn off any lights relied upon for activation of photoluminescent exit signs or path markers.
(7) The lighting control device does not turn off any battery-equipped emergency luminaires, unit equipment, or exit signs.

Be Prepared to Show Compliance at the time of your Fire Alarm Final or Fir Final.

6/18/2020 agedris