SJC Home
Clearance Sheet C2019-005916

 Department IssuesSigned OffIntl

Plan reviewed for new 2,376.56 square feet mini storage building. Reviewed as new storage using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

NOTE: Plans included a check (#1235) for 513.90. The check is attached to the plans cover sheet. Left check with the set of plans (C19-5916).

 

RESUBMITTING:  Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1)  Provide a complete code analysis for this project. NFPA 1: 1.7.12 Please illustrate occupancy type and compliance with the adopted edition of the Florida Fire Prevention Code. Contact an Architect to illustrate Code compliance.

Example of items that need to be addressed: Code and editions, Occupancy of structure/project, fire protection system(s) if included, exit sizes, exit numbers, extinguishers, emergency lights, exit signage, address, light weight truss, what will be in there or processes could present other requirements.  

 

2)  Missing the following pages: Life Safety, Mechanical, Electrical, Plumbing

 

3)  Plans do not indicate illumination of means of egress for the interior corridor. NFPA 101:42.2.8

 

4)  Plans do not indicate Emergency lighting of means of egress for the interior corridor.

Provide the specification sheets and any photometrics for the emergency lights that you are proposing for the building so I can verify coverage. NFPA 101:42.2.9  

 

5)  Need additional exit sign at the end of the long corridor where it turns to the short corridor’s exit door. Include the direction arrow to the exit door. NFPA 101:7.10.2.1

 

6)  Exit signs must match BOTH Electrical page(s) and Life Safety Code page(s).

NOTE: Both Life Safety pages and Electrical pages must match for the emergency lighting and exit signage.

 

7)  The two corridor egress doors (rollup doors) do not meet NFPA 101:42.2.2.2.1, 101:7.2.1.

Provide doors meeting NFPA 101:7.2.1. Any latching / locking hardware shall be in compliance with NFPA 101:7.2.1.5

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

NOTE:  After the review of any resubmittal, additional review comments may be added.

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:
- failure of a public utility or other outside electrical power supply
- opening of a circuit breaker or fuse
- manual act(s), including accidental opening of a switch controlling normal lighting facilities. NFPA 101 7.9.2.3