Plan reviewed for new 1,560 square feet mini storage building with a 392 square foot air conditioned office space. Reviewed as new storage and business - mixed use using FFPC 6th edition effective Dec. 31, 201

Plans included stapled plan set pages 1 through 10 and a separate page A1 which is larger then the stapled set. Page A1 is the office and restroom buildout.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

5/19/2020 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:
- failure of a public utility or other outside electrical power supply
- opening of a circuit breaker or fuse
- manual act(s), including accidental opening of a switch controlling normal lighting facilities. NFPA 101 7.9.2.3

5/19/2020 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish will meet Class A, B or C. 101:38.3.3.2.2

- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:38.3.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

5/19/2020 dfeagle

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

The office door, inside bathroom and the exterior bathroom door hardware shall open the door leaf with no more than one releasing operation. NFPA 1:14.5.2.10.2

The exterior office door and the exterior bathroom's fire rated doors hardware are to be listed for the fire doors fire rating.

5/19/2020 dfeagle