SJC Home
Clearance Sheet C2019-005916*003

 Department IssuesSigned OffIntl

Plan reviewed for new 2,376.56 square feet mini storage building. Reviewed as new storage using FFPC 6th edition effective Dec. 31, 2017.


Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

********************

Thursday, June 11, 2020  Plan review for 1st resubmittal, received page A1.

6/18/2020 agedris

RESUBMITTING:  Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

6/18/2020 agedris

1)  Provide a complete code analysis for this project. NFPA 1: 1.7.12 Please illustrate occupancy type and compliance with the adopted edition of the Florida Fire Prevention Code. Contact an Architect to illustrate Code compliance.

Example of items that need to be addressed: Code and editions, Occupancy of structure/project, fire protection system(s) if included, exit sizes, exit numbers, extinguishers, emergency lights, exit signage, address, light weight truss, what will be in there or processes could present other requirements.

*******************

Thursday, June 11, 2020  Received information on page A1.

6/11/2020 dfeagle

2)  Missing the following pages: Life Safety, Mechanical, Electrical, Plumbing

********************

Thursday, June 11, 2020  Received page A1 containing the Life Safety Plan (LSP). Did not receive any electrical or mechanical pages.

a) Provide missing electrical and mechanical pages.

6/18/2020 agedris

3)  Plans do not indicate illumination of means of egress for the interior corridor. NFPA 101:42.2.8

**********************

Thursday, June 11, 2020  No electrical pages submitted with the 1st resubmittal.

a) Provide the electrical pages showing the lighting for the means of egress.

6/18/2020 agedris

4)  Plans do not indicate Emergency lighting of means of egress for the interior corridor.

Provide the specification sheets and any photometrics for the emergency lights that you are proposing for the building so I can verify coverage. NFPA 101:42.2.9

***********************

Thursday, June 11, 2020  No electrical pages provided.

The emergency lighting provided in the LSP on page A1 appear to be spaced too far apart (29') for wall mounted emergency lighting.

a) Provide the electrical page(s) showing the emergency lighting.

6/18/2020 agedris

5)  Need additional exit sign at the end of the corridor where it turns to the short corridor’s exit door. NFPA 101:7.10.2.1

*********************

Thursday, June 11, 2020    LSP on page A1 shows the exit sign. Need to see it on the electrical page(s).

a) Provide electrical page(s).

6/18/2020 agedris

6)  The door schedule on page 2 of 9 does not have enough information on the type of door (such as wood, metal, etc.), and no hardware schedule noted.

*******************

Thursday, June 11, 2020  None provided.

a) Provide the door and hardware schedules.

6/18/2020 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

NOTE:  After the review of any resubmittal, additional review comments may be added.

6/18/2020 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following:
- failure of a public utility or other outside electrical power supply
- opening of a circuit breaker or fuse
- manual act(s), including accidental opening of a switch controlling normal lighting facilities. NFPA 101 7.9.2.3

6/18/2020 agedris