Plans for a 76 head fire alarm modification to an existing system for a interior remodel. The plans are NOT APPROVED for the following reasons.
----------
Plans APPROVED. pjw Thursday, January 28, 2021
Reviewed using FFPC 6th edition effective Dec. 31, 2017. Reviewer: PJ Webb 904 209 1744 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
1/28/2021
| PWebb |
|
|
Fire Alarm visible notification appliances are required in all areas that are subject to occupancy by those that are hearing impaired. There are several locations that will require devices as follows:
Office 2002 Private 2003 Office 2021 office 2022 office 2025 exam 2041 office 2043 office 2045 lab 2053 office 2065 office 2066 office 2067 office 2074 Office 2076 office 2077 office 2095
NFPA 101:9.6.3.5
------------
Devices added. Devices also added in the to other labs. PJW Thursday, January 28, 2021
|
1/28/2021
| PWebb |
|
|
Double check the coverage in the waiting room. It appears that the rear of the waiting room is outside of the effective range of the device per NFPA 72:18.5.4.1 (a) where it is currently located.
-------
Device added to the rear of the waiting room. PJW Thursday, January 28, 2021
|
1/28/2021
| PWebb |
|
|
The space is designed with a grid of side corridors in addition to the main center corridor. It does not appear that the corridor requirement of NFPA 72:18.5.5.5 are met. There are corridors sections with devices on one end and some with no devices. The corridor rules require devices min 15cd within 15' of each end. When resubmitting add the necessary devices and indicate whether you are designing to the room spacing method or the corridor method as indicated by NFPA 72:18.5.5.5.1. In addition for the main corridor (corridor 2011) there is not a device with 15 feet of the right end of the corridor (if you are using the corridor rules).
----------------
Devices added. Device in main corridor moved so the 15' rule is met. PJW Thursday, January 28, 2021
|
1/28/2021
| PWebb |